Home Table of Contents

§ 690-331. High-voltage underground transmission system

Purdon's Pennsylvania Statutes and Consolidated StatutesTitle 52 P.S. Mines and MiningEffective: January 5, 2009

Purdon's Pennsylvania Statutes and Consolidated Statutes
Title 52 P.S. Mines and Mining (Refs & Annos)
Chapter 12. Bituminous Coal Mine Safety Act of 2008 (Refs & Annos)
Chapter 3. Electrical Equipment
Effective: January 5, 2009
52 P.S. § 690-331
§ 690-331. High-voltage underground transmission system
(a) Underground.--High-voltage cables leading underground and extending underground shall be of the multiple conductor flame-resistant type with a rubber, plastic or armor sheath meeting the requirements of the department for flame resistance. They shall be equipped with metallic shields around each power conductor. One or more ground conductors shall be provided of a total size either:
(1) not less than one-half the power conductor size; or
(2) capable of carrying two times the maximum ground fault current.
There shall also be provided an insulated conductor not smaller than No. 10 AWG for the ground-continuity check circuit. Cables shall be adequate for the intended current and voltage. Splices made in the cable shall provide continuity of all components and shall be made in accordance with the cable manufacturers' recommendations. A competent individual designated by the mine electrician shall supervise the making of splices.
(b) Subject to flexing.--High-voltage cables subject to repeated flexing shall be similar in construction to type SH-D in accordance with Insulated Power Cable Engineers Association standard S-19-81.
(c) Couplers.--If couplers are used, they shall be of the three-phase type with a full metallic shell and shall be adequate for the voltage and current expected. All exposed metal on the couplers shall be grounded to the ground conductor in the cable. The coupler shall be constructed so that the ground continuity conductor shall be broken first and the ground conductor shall be broken last when the coupler is being uncoupled.
(d) Equipment passing over or under cable.--At locations where cables cross haulageways or travelways or where equipment must pass over or under the cable, the cables shall be either installed in a trench in the roof, protected by some mechanical means or buried at least 12 inches below combustible material and adequately protected from crushing by the weight of equipment passing over it.
(e) Location of installation.--High-voltage cables shall be installed only in intake airways. They may be installed on intake haulageways only with the approval of the department. The cable may be installed by hanging on suitable hooks or clamps, supported by a suitable messenger cable, burying or installing in metal conduit. When suspended, the distance between supports shall not exceed 20 feet, and they shall be so placed that they do not damage the cable jacket. When hung in a haulage entry containing a trolley wire, the cable shall be installed at least 12 inches from the trolley wire or feeder wires and away from the track.
(f) Excess cable.--Any excess cable which is connected and supplying a load shall be coiled, stored on a reel or otherwise stored at a place near the load where it can be protected by dangering off the storage area. The cable shall not exceed 1,000 feet in length.
(g) Frames and enclosures.--Frames and enclosures of high-voltage switch units, transformers, metallic cable couplers and splice boxes shall be grounded to the common or primary ground for the system in the high-voltage cable.
(h) Taps or branch circuits.--Taps or branch circuits from the high-voltage feeder shall be made through circuit breakers or suitable load break switches.
(i) Non-load-breaking disconnect switches.--When non-load-breaking disconnect switches are used for sectionalizing high-voltage circuits, they shall be fully metal clad, equipped with a door interlock to break the ground-continuity check circuit, thus tripping the feeding breaker when the door is open, and a voltmeter or indicating lights to verify that the circuit is de-energized before the disconnected switches are opened.
(j) Applicability.--For the purpose of interpretation and compliance with subsection (h) and section 313(h),1 the following apply:
(1) A branch circuit is a subportion of the high-voltage system, serving one or more loads. The branch circuit begins at the junction or splitting of the high-voltage system. The junction consists of the following distinct elements:
(i) Input feeder, which delivers power from the source.
(ii) Output feeder, which may extend the feeder to other parts of the high-voltage system.
(iii) Branch circuit.
The output feeder is not considered as a branch circuit and is not required to have electrical protection at the junction, but receives electrical protection either at the source substation or at some place between the source substation and the junction. The branch circuit is required to have protection at the junction.
(2) A tap supplies power to the high-voltage loads located entirely within the enclosure where the connection is made. Where no splitting of the feeder cable occurs, neither a tap nor branch is created.
(3) A suitable load-break switch, which may be used in lieu of a circuit breaker, is a gang-operated switch with a voltage rating not less than the system voltage capable of interrupting a current equal to its continuous full load rating and to be used in conjunction with fuses to provide overload and short circuit protection for the load being served.

Credits

2008, July 7, P.L. 654, No. 55, § 331, effective in 180 days [Jan. 5, 2009].

Footnotes

52 P.S. § 690-313.
52 P.S. § 690-331, PA ST 52 P.S. § 690-331
Current through Act 13 of the 2024 Regular Session. Some statute sections may be more current, see credits for details.
End of Document