16 CRR-NY 256.13NY-CRR

STATE COMPILATION OF CODES, RULES AND REGULATIONS OF THE STATE OF NEW YORK
TITLE 16. DEPARTMENT OF PUBLIC SERVICE
CHAPTER III. GAS UTILITIES
SUBCHAPTER C. SAFETY
PART 256. INSPECTION AND MAINTENANCE OF GAS HOLDERS
16 CRR-NY 256.13
16 CRR-NY 256.13
256.13 Holder connections and piping.
Valves for connections to holders including relief valves for pressure tanks shall be inspected and tested for opening, closing and leakage at least twice a year. All necessary adjustments and repairs shall be made to restore each item to a high operating efficiency. Gate valves on inlet and outlet connections shall be tested for free movement, and inspection for lubrication of stems and condition of packing at least once a week. Where practicable, control valves shall be provided on inlet and outlet connections at a point distant from the holder, and inlet, outlet and by-pass valves shall be motorized. All piping in proximity to holders shall where practicable be placed underground.
16 CRR-NY 256.13
Current through March 31, 2022