16 CRR-NY 256.10NY-CRR

STATE COMPILATION OF CODES, RULES AND REGULATIONS OF THE STATE OF NEW YORK
TITLE 16. DEPARTMENT OF PUBLIC SERVICE
CHAPTER III. GAS UTILITIES
SUBCHAPTER C. SAFETY
PART 256. INSPECTION AND MAINTENANCE OF GAS HOLDERS
16 CRR-NY 256.10
16 CRR-NY 256.10
256.10 Tar pumping equipment—waterless holders.
Tar and skimmer pumps, including electrical equipment, tar conditioners and tar pipe lines shall be inspected at least once a week for necessary repairs and adjustments. Riser pump run indicators, switches, float rods, and gears of timing device shall be examined and inspected daily. Emergency drives for pumps shall be tested at least once a month to insure immediate availability for service. Records of pump runs shall be taken at least once a day.
16 CRR-NY 256.10
Current through March 31, 2022