16 CRR-NY 255.821NY-CRR
16 CRR-NY 255.821
16 CRR-NY 255.821
255.821 Leaks: nonreportable reading.
Whenever an operator conducts an annual leakage survey of all mains, or a portion of the mains, in its distribution system, any sustained reading of four percent or less gas-in-air on a CGI at an isolated test point outside the curbline or shoulder of the road can be considered a nonreportable reading except where found in manholes, vaults or catch basins.
16 CRR-NY 255.821
Current through March 31, 2022