16 CRR-NY 255.809NY-CRR

STATE COMPILATION OF CODES, RULES AND REGULATIONS OF THE STATE OF NEW YORK
TITLE 16. DEPARTMENT OF PUBLIC SERVICE
CHAPTER III. GAS UTILITIES
SUBCHAPTER C. SAFETY
PART 255. TRANSMISSION AND DISTRIBUTION OF GAS
ACCIDENTS AND LEAKS
16 CRR-NY 255.809
16 CRR-NY 255.809
255.809 Leaks: instrument sensitivity verification.
Each instrument utilized for leakage surveys and investigations must be tested against a known sample or in accordance with the manufacturer's recommended instructions as follows:
(a) after any repair or replacement of parts other than normal maintenance;
(b) once every three months for CGI's and solid-state leak detection instruments and yearly for hydrogen flame ionization (HFI) instruments; and
(c) any time it is suspected that the calibration has changed.
16 CRR-NY 255.809
Current through March 31, 2022
End of Document