16 CRR-NY 255.190NY-CRR

STATE COMPILATION OF CODES, RULES AND REGULATIONS OF THE STATE OF NEW YORK
TITLE 16. DEPARTMENT OF PUBLIC SERVICE
CHAPTER III. GAS UTILITIES
SUBCHAPTER C. SAFETY
PART 255. TRANSMISSION AND DISTRIBUTION OF GAS
DESIGN OF PIPELINE COMPONENTS
16 CRR-NY 255.190
16 CRR-NY 255.190
255.190 Calorimeter or calorimixer structures.
(a) Unmanned structures housing calorimeters or calorimixers shall be designed so that the egress shall be directly to and from the outside, and all air movements shall be directly to and from the outside atmosphere. All associated devices which may vent gas shall be vented through piping to the outside atmosphere.
(b) Unmanned rooms with such gas burning equipment shall be equipped with sensing devices which provide for both the automatic shutdown of the gas supply to such rooms and the signalling of an alarm at a continuously manned post. All alarms shall be immediately investigated.
(c) Combustible material associated with such gas-burning equipment shall be stored safely, and in a manner which separates them from sources of ignition.
16 CRR-NY 255.190
Current through March 31, 2022
End of Document