16 CRR-NY 255.189NY-CRR

OFFICIAL COMPILATION OF CODES, RULES AND REGULATIONS OF THE STATE OF NEW YORK
TITLE 16. DEPARTMENT OF PUBLIC SERVICE
CHAPTER III. GAS UTILITIES
SUBCHAPTER C. SAFETY
PART 255. TRANSMISSION AND DISTRIBUTION OF GAS
DESIGN OF PIPELINE COMPONENTS
16 CRR-NY 255.189
16 CRR-NY 255.189
255.189 Vaults: drainage and waterproofing.
(a) Each vault must be designed so as to minimize the entrance of water. Nevertheless, vault equipment shall be designed to operate safely, if submerged.
(b) A vault containing gas piping may not be connected by means of a drain connection to any other underground structure.
(c) All electrical equipment in vaults must conform to the applicable requirements of Class 1, Group D, of the National Electrical Code, NFPA 70 (as described in section 10.3 of this Title).
16 CRR-NY 255.189
Current through March 31, 2022
End of Document