92.7 Tests for new meters.
(a) All new electricity meters shall be tested and adjusted to an accuracy of as near to 100 percent registration as practical by either the manufacturer of the meter or the meter service provider before installation as specified in the Part 92 Operating Manual.
(b) Where these tests are performed by a manufacturer who maintains a standardizing laboratory, the meter service provider shall take appropriate action to assure that the watthour meters conform the the requirements as specified in the Part 92 Operating Manual.
16 CRR-NY 92.7
Current through February 28, 2023
End of Document |
IMPORTANT NOTE REGARDING CONTENT CURRENCY: The "Current through" date indicated immediately above is the date of the most recently produced official NYCRR supplement covering this rule section. For later updates to this section, if any, please: consult editions of the NYS Register published after this date; or contact the NYS Department of State Division of Administrative Rules at [email protected]. See Help for additional information on the currency of this unofficial version of NYS Rules.