14 CRR-NY 77.4NY-CRR

STATE COMPILATION OF CODES, RULES AND REGULATIONS OF THE STATE OF NEW YORK
TITLE 14. DEPARTMENT OF MENTAL HYGIENE
CHAPTER IV. REGULATION AND QUALITY CONTROL
SUBCHAPTER C. CONSTRUCTION OF FACILITIES
PART 77. STANDARDS FOR PHYSICAL FACILITIES OF HOSPITALS FOR THE MENTALLY ILL, SCHOOLS FOR THE RETARDED, AND ALCOHOL FACILITIES
14 CRR-NY 77.4
14 CRR-NY 77.4
77.4 Safety and sanitation.
(a) There shall be adequate insect screens on all windows to be used for ventilation.
(b) Domestic hot water shall be generated and circulated at 110 degrees Fahrenheit without the use of thermostatically controlled mixing valves and be equipped with a high temperature alarm providing both auditory and visual signals having a set point of 120 degrees Fahrenheit located in an office or other location normally occupied by supervising personnel. Shower mixing valves shall be of the pressure balance type. A separate source of hot water or booster heater shall be provided for kitchens and other appliances and fixtures requiring temperatures in excess of 110 degrees Fahrenheit.
14 CRR-NY 77.4
Current through May 31, 2021
End of Document

IMPORTANT NOTE REGARDING CONTENT CURRENCY: The "Current through" date indicated immediately above is the date of the most recently produced official NYCRR supplement covering this rule section. For later updates to this section, if any, please: consult editions of the NYS Register published after this date; or contact the NYS Department of State Division of Administrative Rules at [email protected]. See Help for additional information on the currency of this unofficial version of NYS Rules.