12 CRR-NY 4-12.5NY-CRR

STATE COMPILATION OF CODES, RULES AND REGULATIONS OF THE STATE OF NEW YORK
TITLE 12. DEPARTMENT OF LABOR
CHAPTER I. INDUSTRIAL BOARD OF APPEALS
SUBCHAPTER A. THE INDUSTRIAL CODE
PART 4. LOW PRESSURE BOILERS
SUBPART 4-12. FLAME SAFEGUARD CONTROL REQUIREMENTS FOR OIL BURNERS INSTALLED AFTER MARCH 31, 1965
12 CRR-NY 4-12.5
12 CRR-NY 4-12.5
4-12.5 Automatic—maximum firing rate over three to seven gallons per hour.
The main flame trial-for-ignition period shall not exceed 30 seconds and the main flame shall be continually supervised while the burner is firing. The electrical circuit to the main fuel valve shall be automatically de-energized within four seconds after flame failure and the de-energized valve shall automatically close within the next five seconds. As an alternative, if intermittent ignition is employed or the ignition system is re-energized in not more than 0.8 second after flame failure, the main oil valve shall close automatically within 30 seconds after flame failure. The burner may make one attempt to relight automatically during this 30-second flame failure reaction time before the valve closes.
12 CRR-NY 4-12.5
Current through March 15, 2022
End of Document

IMPORTANT NOTE REGARDING CONTENT CURRENCY: JULY 31, 2023, is the date of the most recently produced official NYCRR supplement covering this rule section. For later updates to this section, if any, please: consult editions of the NYS Register published after this date; or contact the NYS Department of State Division of Admisnistrative Rules at [email protected]. See Help for additional information on the currency of this unofficial version of the NYS Rules.