SUBPART 4-11. FLAME SAFEGUARD CONTROL REQUIREMENTS FOR ALL OIL BURNERS INSTALLED BEFORE MARCH 31, 1965
12 CRR-NY 4-11.5
12 CRR-NY 4-11.5
4-11.5 Automatic—maximum firing rate over 16 to 33 gallons per hour.
The main flame trial-for-ignition period shall not exceed 15 seconds and the main flame shall be continually supervised while the burner is firing. Upon flame failure, the main oil valve shall close automatically within 15 seconds if the burner does not relight within this time.
12 CRR-NY 4-11.5
Current through March 15, 2022
End of Document

IMPORTANT NOTE REGARDING CONTENT CURRENCY: JULY 31, 2023, is the date of the most recently produced official NYCRR supplement covering this rule section. For later updates to this section, if any, please: consult editions of the NYS Register published after this date; or contact the NYS Department of State Division of Admisnistrative Rules at [email protected]. See Help for additional information on the currency of this unofficial version of the NYS Rules.