12 CRR-NY 4-7.3
12 CRR-NY 4-7.3
4-7.3 Air supply for combustion.
Sufficient fresh air shall be provided to the heat generating apparatus to allow complete combustion of fuel at all firing rates. For gas- or oil-fired burners, the boiler room shall have at least one square foot of opening for the entry of fresh air for every 2,000,000 Btu of fuel burned per hour.
12 CRR-NY 4-7.3
Current through March 15, 2022
End of Document

IMPORTANT NOTE REGARDING CONTENT CURRENCY: JULY 31, 2023, is the date of the most recently produced official NYCRR supplement covering this rule section. For later updates to this section, if any, please: consult editions of the NYS Register published after this date; or contact the NYS Department of State Division of Admisnistrative Rules at [email protected]. See Help for additional information on the currency of this unofficial version of the NYS Rules.