1501.4 Operating temperatures.
(a) Fire detecting devices of the fixed temperature type shall operate when the temperature rises to 165 degrees Fahrenheit, when installed in areas where the maximum temperature at the ceiling is 100 degrees Fahrenheit. Where higher temperatures normally exist at the ceiling, such as in furnaces or boiler rooms, kitchens, laundries, etc., fire detecting devices may operate at higher temperatures providing such higher operating temperatures are commensurate with the ceiling temperatures.
(b) Fire detecting devices of the rate-of-rise type shall operate whenever the rate of the rise in temperature exceeds 20 degrees per minute.
9 CRR-NY 1501.4
Current through September 15, 2021
End of Document

IMPORTANT NOTE REGARDING CONTENT CURRENCY: The "Current through" date indicated immediately above is the date of the most recently produced official NYCRR supplement covering this rule section. For later updates to this section, if any, please: consult editions of the NYS Register published after this date; or contact the NYS Department of State Division of Administrative Rules at [email protected]. See Help for additional information on the currency of this unofficial version of NYS Rules.