599.15 Monitoring of new on-ground and underground piping.
(a) Line leak detectors.
All on-ground or underground piping that conveys hazardous substances under pressure must be equipped with an automatic line leak detector which alerts the operator to the presence of a leak by restricting or shutting off the flow of hazardous substances through the piping or by triggering an audible or visual alarm. These devices must detect leaks equivalent to three gallons per hour at 10 PSIG line pressure within one hour with a probability of detection of 95 percent and a probability of false alarm of five percent or less.
(b) Interstitial monitoring.
All new on-ground and underground piping must be equipped with leak detection equipment capable of detecting leakage between the piping and the secondary containment system.
6 CRR-NY 599.15
Current through February 15, 2022
End of Document

IMPORTANT NOTE REGARDING CONTENT CURRENCY: The "Current through" date indicated immediately above is the date of the most recently produced official NYCRR supplement covering this rule section. For later updates to this section, if any, please: consult editions of the NYS Register published after this date; or contact the NYS Department of State Division of Administrative Rules at [email protected]. See Help for additional information on the currency of this unofficial version of NYS Rules.