6 CRR-NY 225-2.4NY-CRR

STATE COMPILATION OF CODES, RULES AND REGULATIONS OF THE STATE OF NEW YORK
TITLE 6. DEPARTMENT OF ENVIRONMENTAL CONSERVATION
CHAPTER III. AIR RESOURCES
SUBCHAPTER A. PREVENTION AND CONTROL OF AIR CONTAMINATION AND AIR POLLUTION
PART 225. FUEL COMPOSITION AND USE
SUBPART 225-2. FUEL COMPOSITION AND USE—WASTE OIL AS A FUEL
6 CRR-NY 225-2.4
6 CRR-NY 225-2.4
225-2.4 Requirements for owners or operators of facilities proposing to burn waste oil.
As part of an application for a permit or registration to burn waste oil, except as provided in subdivision (d) of this section, owners or operators of facilities must meet the following criteria:
(a) submit an analysis of the waste oil proposed to be burned to the department, pursuant to section 225-2.6 of this Subpart;
(b) a stationary combustion installation or process source that proposes to burn waste oil must have a minimum operating heat input of 20 million Btus per hour or greater;
(c) an incinerator that proposes to burn waste oil must have a minimum charging capacity that equals or exceeds 2,000 pounds per hour of refuse;
(d) an owner or operator of space heaters located in automotive maintenance/service facilities or marine service facilities may burn waste oil and be excepted from the requirements of this section, where the following conditions are met:
(1) the maximum operating heat input is less than 500,000 Btus per hour;
(2) the waste oil is generated on site (this includes waste oils generated by do-it-yourself customers that the facility is required to accept) or at another facility under common ownership; and
(3) the waste oil meets the criteria in section 225-2.5 Table 1 of this Subpart, except that lead may not exceed 25 parts per million (ppm) by weight (water free basis) of fuel.
6 CRR-NY 225-2.4
Current through December 31, 2021
End of Document