§ 60306. Use of Recycled Water for Cooling.

22 CA ADC § 60306BARCLAYS OFFICIAL CALIFORNIA CODE OF REGULATIONS

Barclays Official California Code of Regulations Currentness
Title 22. Social Security
Division 4. Environmental Health
Chapter 3. Water Recycling Criteria
Article 3. Uses of Recycled Water
22 CCR § 60306
§ 60306. Use of Recycled Water for Cooling.
(a) Recycled water used for industrial or commercial cooling or air conditioning that involves the use of a cooling tower, evaporative condenser, spraying or any mechanism that creates a mist shall be a disinfected tertiary recycled water.
(b) Use of recycled water for industrial or commercial cooling or air conditioning that does not involve the use of a cooling tower, evaporative condenser, spraying, or any mechanism that creates a mist shall be at least disinfected secondary-23 recycled water.
(c) Whenever a cooling system, using recycled water in conjunction with an air conditioning facility, utilizes a cooling tower or otherwise creates a mist that could come into contact with employees or members of the public, the cooling system shall comply with the following:
(1) A drift eliminator shall be used whenever the cooling system is in operation.
(2) A chlorine, or other, biocide shall be used to treat the cooling system recirculating water to minimize the growth of Legionella and other micro-organisms.
Note: Authority cited: Section 13521, Water Code. Reference: Sections 13520 and 13521, Water Code.
HISTORY
1. New section filed 11-2-2000; operative 12-2-2000 (Register 2000, No. 44).
This database is current through 8/9/19 Register 2019, No. 32
22 CCR § 60306, 22 CA ADC § 60306