§ 2644.1. Enhanced Leak Detection.
23 CA ADC § 2644.1Barclays Official California Code of Regulations
23 CCR § 2644.1
§ 2644.1. Enhanced Leak Detection.
(2) The enhanced leak detection test method shall be third party certified, in accordance with section 2643(f), for the capability of detecting both vapor and liquid phase releases from the underground storage tank system. The enhanced leak detection test method shall be capable of detecting a leak rate of at least 0.005 gallons per hour, with a probability of detection of at least 95 percent and a probability of false alarm no greater than five percent.
(3) Owners and operators subject to the requirements of this section shall have a program of enhanced leak detection reviewed and approved by the local agency within six months following notification by the board. The enhanced leak detection shall be implemented no later than 18 months following receipt of notification from the board and repeated every 36 months thereafter.
Credits
Note: Authority cited: Sections 25299.3 and 25299.7, Health and Safety Code. Reference: Sections 25283, 25291, 25292, 25292.4 and 25404, Health and Safety Code; and 40 CFR §§ 280.40 and 280.41.
History
1. New section filed 5-14-2001; operative 5-14-2001 pursuant to Government Code section 11343.4 (Register 2001, No. 20).
2. Amendment of subsection (a)(5) and amendment of Note filed 10-13-2016; operative 1-1-2017 (Register 2016, No. 42).
3. Amendment of subsections (a) and (a)(2)-(4) filed 8-27-2018; operative 10-1-2018 (Register 2018, No. 35).
This database is current through 6/7/24 Register 2024, No. 23.
Cal. Admin. Code tit. 23, § 2644.1, 23 CA ADC § 2644.1