Home Table of Contents

§ 2643.1. Tank Integrity Testing Requirements.

23 CA ADC § 2643.1Barclays Official California Code of Regulations

Barclays California Code of Regulations
Title 23. Waters
Division 3. State Water Resources Control Board and Regional Water Quality Control Boards
Chapter 16. Underground Tank Regulations
Article 4. Existing Underground Storage Tank Monitoring Requirements
23 CCR § 2643.1
§ 2643.1. Tank Integrity Testing Requirements.
Tank integrity testing shall meet the requirements of section 2643(f) and shall be conducted using one of the two methods in subsections (a) or (b) below. Tank integrity test methods shall account for the effects of thermal expansion or contraction of the product, vapor pockets, tank deformation, evaporation or condensation, and the presence of water in the backfill:
(a) A volumetric tank integrity test shall be capable of detecting a release of 0.1 gallon per hour from any portion of the tank when the tank is at least 65% full of product or at any product level if the product-filled portion of the tank is tested under pressure equivalent to that of a full tank. If any volumetric tank integrity test is conducted at a product level lower than the overfill protection device set point, a test meeting the requirements of subsection (b) must be used to test the ullage portion of the tank.
(b) A nonvolumetric tank integrity test shall be capable of detecting a release of 0.1 gallon per hour from any portion of the tank at any product level.

Credits

Note: Authority cited: Sections 25299.3 and 25299.7, Health and Safety Code. Reference: Section 25292, Health and Safety Code; and 40 CFR 280.40 - 280.45.
History
1. New section filed 4-5-94; operative 5-5-94 (Register 94, No. 14).
2. Editorial correction of History 1 (Register 2000, No. 31).
This database is current through 6/7/24 Register 2024, No. 23.
Cal. Admin. Code tit. 23, § 2643.1, 23 CA ADC § 2643.1
End of Document