§ 2641. Monitoring Program Requirements.
23 CA ADC § 2641Barclays Official California Code of Regulations
23 CCR § 2641
§ 2641. Monitoring Program Requirements.
(d) All portions of the underground storage tank system shall be visually monitored in accordance with section 2642. A portion of the underground storage tank shall be exempt from visual monitoring if the owner demonstrates to the satisfaction of the local agency that one or more of the following conditions apply to that portion:
(e) Non-visual monitoring shall be implemented for all portions of the underground storage tank which are exempt under subsection (d) and, for the underground storage tank, during periods when visual monitoring required under subsection (d) is not conducted. This non-visual monitoring shall include a quantitative release detection method as specified in section 2643 or a qualitative release detection method as specified in section 2644 or a combination of these methods as approved by the local agency.
(g) The monitoring program shall be approved by the local agency and shall be in compliance with the requirements of this article and with the underground storage tank operating permit. The local agency may require additional monitoring methods specified in the operating permit or more frequent monitoring as necessary to satisfy the objective in subsection (a). In deciding whether to approve a proposed monitoring program, or to require additional methods or more frequent monitoring, the local agency shall consider the following factors:
(k) When an unauthorized release is indicated during the installation of a release detection system, the owner or operator shall comply with the release reporting requirements of Article 5 and, if the release came from the existing tank, shall cease the installation process until the tank system is replaced, repaired, upgraded, or closed in accordance with the applicable provisions of this chapter.
(l) When implementation of the monitoring program, or any condition, indicates that an unauthorized release may have occurred, the owner or operator shall comply with the release reporting requirements of Article 5 and shall replace, repair, or close the underground storage tank in accordance with the applicable provisions of this chapter.
Credits
Note: Authority cited: Sections 25299.3 and 25299.7, Health and Safety Code. Reference: Sections 25283, 25284.1, 25291 and 25292, Health and Safety Code; 40 CFR 280.40 and 280.41.
History
1. Editorial correction of printing errors in Tables 4.1 and 4.2 (Register 86, No. 23).
2. Change without regulatory effect of Table 4.1 (Register 86, No. 40).
3. Repealer and new section filed 8-9-91 as an emergency; operative 8-9-91. Text remains in effect uninterrupted pursuant to Health and Safety Code section 25299.7 (Register 92, No. 14).
4. Editorial correction of printing errors in History 3 (Register 92, No. 43).
5. Amendment filed 4-5-94; operative 5-5-94 (Register 94, No. 14).
6. Amendment of subsection (j) and amendment of Note filed 5-14-2001; operative 5-14-2001 pursuant to Government Code section 11343.4 (Register 2001, No. 20).
7. Amendment of subsections (j) filed 4-8-2004; operative 5-8-2004 (Register 2004, No. 15).
This database is current through 6/7/24 Register 2024, No. 23.
Cal. Admin. Code tit. 23, § 2641, 23 CA ADC § 2641
End of Document |