§ 4054.3. T. Tolerances.
4 CA ADC § 4054.3Barclays Official California Code of Regulations
Barclays California Code of Regulations
Title 4. Business Regulations
Division 9. Division of Measurement Standards, Department of Food and Agriculture
Chapter 2. Special Equipment
Article 2. Procedures for Type Approval Certification Evaluation and Field Compliance Testing of Vapor Recovery Systems
4 CCR § 4054.3
§ 4054.3. T. Tolerances.
The required, additional attempts, in total, to override any nozzle primary shut-off device shall not increase the dispenser volume indication by more than 1/10 gallon.
With the vapor return line blocked by fuel (simulating recirculation due to primary shut-off device failure), each attempt to dispense fuel shall result in automatic nozzle shut off before the dispenser volume indication increases more than 3/10 gallon.
Assist vapor recovery systems shall operate at the inches of H2O column vacuum recommended by the manufacturer, but shall not exceed -10 inches of H2O column vacuum for nozzles where the spout is booted and can form a closed seal around the vehicle filler neck.
The quantity of measured liquid collected in the vapor return line/lines shall not exceed both:
Credits
Note: Authority cited: Sections 12107 and 12500.5, Business and Professions Code; and Sections 41956(a) and 41956(c), Health and Safety Code. Reference: Sections 12107 and 12500.5, Business and Professions Code; and Sections 41956(a) and 41956(c), Health and Safety Code.
History
1. Repealer and new section filed 8-1-91; operative 9-2-91 (Register 92, No. 9).
2. Amendment of subsection T.2. filed 5-7-97; operative 6-6-97 (Register 97, No. 19).
This database is current through 4/26/24 Register 2024, No. 17.
Cal. Admin. Code tit. 4, § 4054.3, 4 CA ADC § 4054.3