§ 66264.345. Operating Requirements.
(a) An incinerator shall be operated in accordance with operating requirements specified in the permit. These will be specified on a case-by-case basis as those demonstrated (in a trial burn or in alternative data as specified in section 66264.344(b) and included with Part B of a facility's permit application) to be sufficient to comply with the performance standards of section 66264.343.
(b) Each set of operating requirements will specify the composition of the waste feed (including acceptable variations in the physical or chemical properties of the waste feed which will not affect compliance with the performance requirement of section 66264.343) to which the operating requirements applynt of section 66264.343) to which the operating requirements apply. For each such waste feed, the permit will specify acceptable operating limits including the following conditions:
(1) carbon monoxide (CO) level in the stack exhaust gas;
(2) waste feed rate;
(3) combustion temperature;
(4) an appropriate indicator of combustion gas velocity;
(5) allowable variations in incinerator system design or operating procedures; and
(6) such other operating requirements as are necessary to ensure the performance standards of section 66264.343 are met.
(c) During start-up and shut-down of an incinerator, hazardous waste (except wastes exempted in accordance with section 66264.340) shall not be fed into the incinerator unless the incinerator is operating within the conditions of operation (temperature, air feed rate, etc.) specified in the permit.
(d) Fugitive emissions from the combustion zone shall be controlled by:
(1) keeping the combustion zone totally sealed against fugitive emissions; or
(2) maintaining a combustion zone pressure lower than atmospheric pressure; or
(3) an alternate means of control demonstrated (with Part B of the permit application) to provide fugitive emissions control equivalent to maintenance of combustion zone pressure lower than atmospheric pressure.
(e) An incinerator shall be operated with a functioning system to automatically cut off waste feed to the incinerator when operating conditions deviate from limits established under subsection (a) of this section.
(f) An incinerator shall cease operation when changes in waste feed, incinerator design, or operating conditions exceed limits designated in its permit.

Credits

Note: Authority cited: Sections 208 and 25159, Health and Safety Code. Reference: Sections 25159.5 and 25200, Health and Safety Code; 40 CFR Section 264.345.