§ 73647. Gases for Medical Use.

22 CA ADC § 73647Barclays Official California Code of RegulationsEffective: May 30, 2023

Barclays California Code of Regulations
Title 22. Social Security
Division 5. Licensing and Certification of Health Facilities, Home Health Agencies, Clinics, and Referral Agencies (Refs & Annos)
Chapter 4. Intermediate Care Facilities
Article 5. Physical Plant
Effective: May 30, 2023
22 CCR § 73647
§ 73647. Gases for Medical Use.
(a) Gases for medical use covered by this section are: carbon dioxide, cyclopropane, ethylene, helium, nitrous oxide, oxygen, helium-oxygen mixtures and carbon dioxide-oxygen mixtures.
(b) Provision shall be made for safe handling and storage of medical gas cylinders.
(c) Transfer of gas by facility personnel from one cylinder to another shall be prohibited.
(d) All medical gas cylinders, pressure regulators, wall outlets from piping systems and external removable connection hoses used therewith shall, by physical design, be so constructed that connections for different gases are not interchangeable. This standardization shall be accomplished by installing permanent fittings as indicated in this section:
(1) Outlet valves for small compressed gas cylinders (Style E and smaller) shall conform with the Pin Index Safety System contained in “V-1: Standard for Compressed Gas Cylinder Valve Outlet and Inlet Connections” 15th Edition (2021), by the Compressed Gas Association and the American National Standards Institute, hereby incorporated by reference.
(2) Valve outlet connections for large cylinders (Style F and larger) for oxygen and nitrous oxide shall conform with the standards contained in “V-1: Standard for Compressed Gas Cylinder Valve Outlet and Inlet Connections” 15th Edition (2021), by the Compressed Gas Association and the American National Standards Institute, hereby incorporated by reference. Standard Connection No. 540 shall be used with oxygen cylinders and Standard Connection No. 326 shall be used with nitrous oxide cylinders.
(3) Removable exposed threaded connections, where employed in medical gas piping systems and equipment used in conjunction with resuscitators and oxygen therapy apparatus, shall be provided with noninterchangeable connections which conform with Pamphlet “V-5: Diameter-Index Safety System (Noninterchangeable Low Pressure Connections for Medical Gas Applications)” 7th Edition (2019) by the Compressed Gas Association, hereby incorporated by reference.
(4) Station outlets from piped oxygen and nitrous oxide systems shall conform with the standards contained in “NFPA 99: Health Care Facilities Code” (2012) by the National Fire Protection Association, hereby incorporated by reference.
(5) Removable connection hoses from outlets shall be fitted with permanently connected fittings to match the standards listed above in subsections (1), (2), (3) and (4).
(e) The piped oxygen or nitrous oxide system(s) shall be tested in accordance with the National Fire Protection Association Bulletin, NFPA 99, referred to above, and a written report shall be maintained in each of the following instances:
(1) Upon completion of initial installation.
(2) Whenever changes are made to a system.
(3) Whenever the integrity of a system has been breached.
(4) At least annually.
(f) Oxygen Equipment.
(1) Vaporizer bottles on oxygen equipment shall be sterilized after each use.
(2) Only sterile distilled water shall be used in vaporizer bottles.
(3) Vaporizer bottles shall be changed at least every 24 hours.