Home Table of Contents

§ 64432. Monitoring and Compliance--Inorganic Chemicals.

22 CA ADC § 64432Barclays Official California Code of Regulations

Barclays California Code of Regulations
Title 22. Social Security
Division 4. Environmental Health
Chapter 15. Domestic Water Quality and Monitoring Regulations
Article 4. Primary Standards--Inorganic Chemicals
22 CCR § 64432
§ 64432. Monitoring and Compliance--Inorganic Chemicals.
(a) All public water systems shall monitor to determine compliance with the nitrate and nitrite MCLs in table 64431-A, pursuant to subsections (d) through (f) and section 64432.1. All community and nontransient-noncommunity water systems shall monitor to determine compliance with the perchlorate MCL, pursuant to subsections (d), (e), and (l), and section 64432.3. All community and nontransient-noncommunity water systems shall also monitor to determine compliance with the other MCLs in table 64431-A, pursuant to subsections (b) through (n), and, for asbestos, section 64432.2. Monitoring shall be conducted in the year designated by the State Board of each compliance period beginning with the compliance period starting January 1, 1993.
(b) Unless directed otherwise by the State Board, each community and nontransient-noncommunity water system shall initiate monitoring for an inorganic chemical within six months following the effective date of the regulation establishing the MCL for the chemical and the addition of the chemical to table 64431-A.
If otherwise performed in accordance with this section, groundwater monitoring for an inorganic chemical performed no more than two years prior to the effective date of the regulation establishing the MCL may be used to satisfy the requirement for initiating monitoring within six months following such effective date.
(c) Unless more frequent monitoring is required pursuant to this Chapter, the frequency of monitoring for the inorganic chemicals listed in table 64431-A, except for asbestos, nitrate/nitrite, and perchlorate, shall be as follows:
(1) Each compliance period, all community and nontransient-noncommunity systems using groundwater shall monitor once during the year designated by the State Board. The State Board will designate the year based on historical monitoring frequency and laboratory capacity. All community and nontransient-noncommunity systems using approved surface water shall monitor annually. All systems monitoring at distribution entry points which have combined surface and groundwater sources shall monitor annually.
(2) Quarterly samples shall be collected and analyzed for any chemical if analyses of such samples indicate a continuous or persistent trend toward higher levels of that chemical, based on an evaluation of previous data.
(d) For the purposes of sections 64432, 64432.1, 64432.2, and 64432.3, detection shall be defined by the detection limits for purposes of reporting (DLRs) in table 64432-A.
Table 64432-A
Detection Limits for Purposes of Reporting (DLRs) for Regulated Inorganic Chemicals
Chemical
Detection Limit for Purposes of Reporting (DLR) (mg/L)
Aluminum
0.05
Antimony
0.006
Arsenic
0.002
Asbestos
0.2
MFL>10μm*
Barium
0.1
Beryllium
0.001
Cadmium
0.001
Chromium
0.01
Cyanide
0.1
Fluoride
0.1
Mercury
0.001
Nickel
0.01
Nitrate (as nitrogen)
0.4
Nitrite (as nitrogen)
0.4
Perchlorate
0.002
0.001
(Effective January 1, 2024)
Selenium
0.005
Thallium
0.001
*  MFL=million fibers per liter; DLR for fibers exceeding 10 μm in length.
(e) Samples shall be collected from each water source or a supplier may collect a minimum of one sample at every entry point to the distribution system which is representative of each source after treatment. The system shall collect each sample at the same sampling site, unless a change is approved by the State Board.
(f) A water system may request approval from the State Board to composite samples from up to five sampling sites, provided that the number of sites to be composited is less than the ratio of the MCL to the DLR. Approval will be based on a review of three years of historical data, well construction and aquifer information for groundwater, and intake location, similarity of sources, and watershed characteristics for surface water. Compositing shall be done in the laboratory.
(1) Systems serving more than 3,300 persons shall composite only from sampling sites within a single system. Systems serving 3,300 persons or less may composite among different systems up to the 5-sample limit.
(2) If any inorganic chemical is detected in the composite sample at a level equal to or greater than one fifth of the MCL, a follow-up sample shall be analyzed within 14 days from each sampling site included in the composite for the contaminants which exceeded the one-fifth-MCL level. If available, duplicates of the original sample taken from each sampling site used in the composite may be used instead of resampling; the analytical results shall be reported within 14 days. The water supplier may collect up to two additional samples each from one or more of the sources to confirm the result(s).
(3) Compliance for each site shall be determined on the basis of the individual follow-up samples, or on the average of the follow-up and confirmation sample(s) if the supplier collects confirmation sample(s) for each detection.
(g) If the level of any inorganic chemical, except for nitrate, nitrite, nitrate plus nitrite, or perchlorate, exceeds the MCL, the water supplier shall do one of the following:
(1) Inform the State Board within 48 hours and monitor quarterly beginning in the next quarter after the exceedance occurred; or
(2) Inform the State Board within seven days from the receipt of the analysis and, as confirmation, collect one additional sample within 14 days from receipt of the analysis. If the average of the two samples collected exceeds the MCL, this information shall be reported to the State Board within 48 hours and the water supplier shall monitor quarterly beginning in the next quarter after the exceedance occurred.
(h) If the concentration of an inorganic chemical exceeds ten times the MCL, within 48 hours of receipt of the result the water supplier shall notify the State Board and resample as confirmation. The water supplier shall notify the State Board of the result(s) of the confirmation sample(s) within 24 hours of receipt of the confirmation result(s).
(1) If the average concentration of the original and confirmation sample(s) is less than or equal to ten times the MCL, the water supplier shall monitor quarterly beginning in the quarter following the quarter in which the exceedance occurred.
(2) If the average concentration of the original and confirmation sample(s) exceeds ten times the MCL, the water supplier shall, if directed by the State Board;
(A) Immediately discontinue use of the contaminated water source; and
(B) Not return the source to service without written approval from the State Board.
(i) Compliance with the MCLs shall be determined by a running annual average; if any one sample would cause the annual average to exceed the MCL, the system is immediately in violation. If a system takes more than one sample in a quarter, the average of all the results for that quarter shall be used when calculating the running annual average. If a system fails to complete four consecutive quarters of monitoring, the running annual average shall be based on an average of the available data.
(j) If a system using groundwater has collected a minimum of two quarterly samples or a system using approved surface water has collected a minimum of four quarterly samples and the sample results have been below the MCL, the system may apply to the State Board for a reduction in monitoring frequency.
(k) Water quality data collected prior to January 1, 1990, and/or data collected in a manner inconsistent with this section shall not be used in the determination of compliance with the monitoring requirements for inorganic chemicals.
(l) Water quality data collected in compliance with the monitoring requirements of this section by a wholesaler providing water to a public water system shall be acceptable for use by that system for compliance with the monitoring requirements of this section.
(m) A water system may apply to the State Board for a waiver from the monitoring frequencies specified in subsection (c)(1), if the system has conducted at least three rounds of monitoring (three periods for groundwater sources or three years for approved surface water sources) and all previous analytical results are less than the MCL. The water system shall specify the basis for its request. If granted a waiver, a system shall collect a minimum of one sample per source while the waiver is in effect and the term of the waiver shall not exceed one compliance cycle (i.e., nine years).
(n) A water system may be eligible for a waiver from the monitoring frequencies for cyanide specified in subsection (c)(1) without any prior monitoring if it is able to document that it is not vulnerable to cyanide contamination pursuant to the requirements in section 64445(d)(1) or (d)(2).
(o) Transient-noncommunity water systems shall monitor for the inorganic chemicals in table 64431-A as follows:
(1) All sources shall be monitored at least once for fluoride; and
(2) Surface water sources for parks and other facilities with an average daily population use of more than 1,000 people and/or which are determined to be subject to potential contamination based on a sanitary survey shall be monitored at the same frequency as community water systems.

Credits

Note: Authority cited: Sections 116271, 116275, 116293(b), 116350 and 116375, Health and Safety Code. Reference: Sections 116275 and 116385, Health and Safety Code.
History
1. New section filed 9-8-94 as an emergency; operative 9-8-94 (Register 94, No. 36). A Certificate of Compliance must be transmitted to OAL by 1-6-95 or emergency language will be repealed by operation of law on the following day.
2. New section refiled 1-3-95 as an emergency; operative 1-3-95 (Register 95, No. 1). A Certificate of Compliance must be transmitted to OAL by 5-3-95 or emergency language will be repealed by operation of law on the following day.
3. New section refiled 4-26-95 as an emergency; operative 4-26-95 (Register 95, No. 17). A Certificate of Compliance must be transmitted to OAL by 8-24-95 or emergency language will be repealed by operation of law on the following day.
4. Certificate of Compliance as to 4-26-95 order including amendment of subsection (b)(1), Table 64432-A, and subsections (e)(1)-(2) and (k) transmitted to OAL 5-5-95 and filed 6-19-95 (Register 95, No. 25).
5. Amendment of subsections (a) and (b) and table 64432-A and amendment of Note filed 3-23-98; operative 4-22-98 (Register 98, No. 13).
6. Amendment of subsections (a), (b), (c), (f), (j) and (m) and amendment of Note filed 9-18-2007; operative 10-18-2007 (Register 2007, No. 38).
7. Amendment of subsection (a), new subsections (b) and (h)-(h)(2)(B),, subsection relettering and amendment of newly designated subsections (c), (g)(1)-(2), (i), (m) and (n) and amendment of Note filed 10-29-2008; operative 11-28-2008 (Register 2008, No. 44).
8. Change without regulatory effect amending subsection (a) filed 4-21-2011 pursuant to section 100, title 1, California Code of Regulations (Register 2011, No. 16).
9. Amendment of section and Note filed 5-28-2014; operative 7-1-2014 (Register 2014, No. 22).
10. Change without regulatory effect amending subsections (a), (b), (c)(1), (e)-(f), (g)-(h), (h)(2), (h)(2)(B), (j) and (m) and amending Note filed 6-2-2015 pursuant to section 100, title 1, California Code of Regulations (Register 2015, No. 23).
11. Editorial correction of Note (Register 2015, No. 29).
12. Change without regulatory effect amending Table 64432-A filed 7-16-2015 pursuant to section 100, title 1, California Code of Regulations (Register 2015, No. 29).
13. Change without regulatory effect repealing subsection (b)(1) designator and subsection (b)(2) and amending Table 64432-A filed 9-11-2017 pursuant to section 100, title 1, California Code of Regulations (Register 2017, No. 37).
14. Amendment of Table 64432-A and Note filed 6-17-2021; operative 7-1-2021 pursuant to Government Code section 11343.4(b)(3) (Register 2021, No. 25). Transmission deadline specified in Government Code section 11346.4(b) extended 60 calendar days pursuant to Executive Order N-40-20.
This database is current through 4/26/24 Register 2024, No. 17.
Cal. Admin. Code tit. 22, § 64432, 22 CA ADC § 64432
End of Document