§ 60304. Use of Recycled Water for Irrigation.
22 CA ADC § 60304Barclays Official California Code of Regulations
22 CCR § 60304
§ 60304. Use of Recycled Water for Irrigation.
(a) Recycled water used for the surface irrigation of the following shall be a disinfected tertiary recycled water, except that for filtration pursuant to Section 60301.320(a) coagulation need not be used as part of the treatment process provided that the filter effluent turbidity does not exceed 2 NTU, the turbidity of the influent to the filters is continuously measured, the influent turbidity does not exceed 5 NTU for more than 15 minutes and never exceeds 10 NTU, and that there is the capability to automatically activate chemical addition or divert the wastewater should the filter influent turbidity exceed 5 NTU for more than 15 minutes:
Credits
Note: Authority cited: Section 13521, Water Code. Reference: Sections 13520 and 13521, Water Code.
History
1. New section filed 11-2-2000; operative 12-2-2000 (Register 2000, No. 44).