§ 5447. Dry Type Overspray Collectors (Exhaust Air Filters).
8 CA ADC § 5447Barclays Official California Code of Regulations
8 CCR § 5447
§ 5447. Dry Type Overspray Collectors (Exhaust Air Filters).
(1) Visible gauges or audible alarms or pressure activated devices shall be installed to indicate or insure that the required air velocity is maintained. (See Section 5153). Dry spray booth equipped with a filter roll which is automatically advanced when the air velocity is reduced to that specified in this Section shall be arranged to cause shutdown of spraying operations if the filter roll fails to advance automatically.
(2) Maintenance procedures shall be established to assure replacing filter pads before excessive restriction to air flow occurs. Filter pads shall be inspected after each period of use and clogged filter pads discarded and replaced. Filter rolls shall be inspected to insure proper replacement of filter media.
Credits
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.
History
1. Amendment of subsections (a) (1) and (4) filed 12-5-86; effective thirtieth day thereafter (Register 86, No. 51).
This database is current through 6/21/24 Register 2024, No. 25.