§ 1773.1. Production Facility Secondary Containment.

14 CA ADC § 1773.1Barclays Official California Code of Regulations

Barclays California Code of Regulations
Title 14. Natural Resources
Division 2. Department of Conservation
Chapter 4. Development, Regulation, and Conservation of Oil and Gas Resources (Refs & Annos)
Subchapter 2. Environmental Protection
Article 3. Requirements
14 CCR § 1773.1
§ 1773.1. Production Facility Secondary Containment.
(a) All production facilities storing and/or processing fluids, except valves, headers, manifolds, pumps, compressors, wellheads, pipelines, flowlines and gathering lines shall have secondary containment.
(b) Secondary containment shall be capable of containing the equivalent volume of liquids from the single piece of equipment with the largest gross capacity within the secondary containment.
(c) Secondary containment shall be capable of confining liquid for a minimum of 72 hours.
(d) When not in use for rain water management, rain water valves on a secondary containment shall be closed and secured to prevent unauthorized use.
(e) All damage to secondary containment shall be repaired immediately.
(f) The requirements of this section are not applicable until six months after the effective date of this regulation.

Credits

Note: Authority cited: Sections 3013 and 3270, Public Resources Code. Reference: Sections 3106 and 3270, Public Resources Code.
History
1. New section filed 12-30-2010; operative 1-29-2011 (Register 2010, No. 53).