§ 2268. Pipe Size.
25 CA ADC § 2268Barclays Official California Code of Regulations
25 CCR § 2268
§ 2268. Pipe Size.
Table 2268-1 |
Drainage Pipe Diameter and Number of Fixture Units on Drainage System |
Maximum No. | Maximum No. | Terminal & | |
of Fixture Units | of Fixture Units | Relief Vent | |
Size of Drainage | Individually | Wet Vented | Wet Vented |
Pipe (Inches) | Vented System | System | System (Inches) |
3 | 35 | 14 | 2 |
4 | 180 | 35 | 3 |
5 | 356 | 180 | 4 |
6 | 600 | 356 | 4 |
Table 2268-2 |
Minimum Grade and Slope of Drainage Pipe |
Slope | Slope | ||
Pipe Size | per 100 ft. | Pipe Size | per 100 ft. |
(inches) | (inches) | (inches) | (inches) |
2 | 25 | 6 | 8 | ||
3 | 20 | 8 | 4 | ||
4 | 15 | 10 | 3 ½ | ||
5 | 11 | 12 | 3 |
Credits
Note: Authority cited: Section 18865, Health and Safety Code. Reference: Section 18873.1, Health and Safety Code.
History
1. New section filed 7-6-2004; operative 7-6-2004 pursuant to Government Code section 11343.4 (Register 2004, No. 28).
This database is current through 5/10/24 Register 2024, No. 19.
Cal. Admin. Code tit. 25, § 2268, 25 CA ADC § 2268