(a) When gas meters are installed, they shall not depend on the gas riser outlet for support. Gas meters shall be adequately supported by a post and bracket or by other means approved by the enforcement agency.
(b) Meters shall not be installed beneath units, in unventilated or inaccessible locations, or closer than three (3) feet from sources of ignition. The unit electrical service equipment shall not be considered a source of ignition when not enclosed in the same compartment with a gas meter.
(c) All gas meter installations shall be provided with a shutoff valve or cock located adjacent to and on the inlet side of the meter. In the case of a single meter installation utilizing an LPG tank, the tank service valve may be used in lieu of the shutoff valve or cock.
(d) Each meter installed shall be in a readily accessible location and shall be provided with unions or other fittings so as to be easily removed and replaced while maintaining an upright position.

Credits

Note: Authority cited: Sections 18865 and 18873.4, Health and Safety Code. Reference: Section 18873.4, Health and Safety Code.
History
1. New section filed 7-6-2004; operative 7-6-2004 pursuant to Government Code section 11343.4 (Register 2004, No. 28).
2. Amendment of subsection (c) and repealer of subsection (e) filed 7-22-2005; operative 7-22-2005 pursuant to Government Code section 11343.4 (Register 2005, No. 29).
3. Editorial correction of History 2 (Register 2005, No. 33).
This database is current through 5/10/24 Register 2024, No. 19.
Cal. Admin. Code tit. 25, § 2226, 25 CA ADC § 2226
End of Document