§ 1312. Private Systems.
(a) In areas where fire department services are not available, as determined by the enforcement agency, a private fire protection system shall be installed and maintained consisting of hydrant or wet standpipe risers connected to the park water main or a separate system capable of delivering seventy-five (75) gallons per minute at thirty (30) psi with at least two lines open, in addition to the normal requirements of the park, and with the hydrants or wet standpipes located within seventy-five (75) feet of each lot. Each hydrant or wet standpipe shall be provided with an approved one-and-one-half (1 ½ ) inch hose valve and connection with one, one-and-one-half (1 ½ ) inch national standard male outlet and shall have connected thereto a minimum of seventy-five (75) feet of one and one-half (1 ½ ) inch cotton or dacron jacketed rubber lined fire hose with an approved cone type nozzle with a minimum one-half ( ½ ) inch orifice. The fire hose shall be mounted on an approved hose rack or reel enclosed in a weather resistant cabinet which shall be painted red and marked “FIRE HOSE” in four (4) inch letters of contrasting color.
(b) In parks constructed prior to September 1, 1968 that have hydrants installed, the hydrants shall be provided with not less than thirty-five (35) pounds water pressure. These hydrants must meet the hose requirements contained in subsection (a) of this section, but are not required to meet the water flow requirements contained in subsection 1316(c) of this Article. In the event this water pressure is not available, seventy-five (75) feet of three-quarter ( ¾ ) inch hose with attached cast brass adjustable spray stream, shut-off nozzle, in a weather-protected cabinet which must deliver four and one-half (4.5) gallons of water per minute at any given point within the mobilehome park, may be substituted for one and one-half (1 ½ ) inch diameter hose as specified herein.

Credits

Note: Authority cited: Sections 18300, 18610 and 18691, Health and Safety Code. Reference: Sections 18610 and 18691, Health and Safety Code.
History
1. Amendment filed 8-22-85; effective upon filing pursuant to Government Code Section 11346.2(d) (Register 85, No. 36).
2. Amendment filed 7-6-2004; operative 7-6-2004 pursuant to Government Code section 11343.4 (Register 2004, No. 28).
3. Amendment filed 1-21-2009; operative 1-21-2009 pursuant to Government Code section 11343.4 (Register 2009, No. 4).