§ 1268. Pipe Size.
25 CA ADC § 1268Barclays Official California Code of Regulations
25 CCR § 1268
§ 1268. Pipe Size.
TABLE 1268-1 |
Drainage Pipe Diameter and Number of Fixture Units on Drainage System |
Size of Drainage Pipe (Inches) | Maximum No. of Fixture Units Individually Vented System | Maximum No. of Fixture Units Wet Vented System | Terminal & Relief Vent Wet Vented System (Inches) |
3 | 35 | 14 | 2 |
4 | 180 | 35 | 3 |
5 | 356 | 180 | 4 |
6 | 600 | 356 | 4 |
TABLE 1268-2 |
Minimum Grade and Slope of Drainage Pipe |
Pipe Size (inches) | Slope per 100 ft. (inches) | Pipe Size (inches) | Slope per 100 ft. (inches) |
2 | 25 | 6 | 8 | ||
3 | 20 | 8 | 4 | ||
4 | 15 | 10 | 3 ½ | ||
5 | 11 | 12 | 3 |
Credits
Note: Authority cited: Section 18300, Health and Safety Code. Reference: Section 18630, Health and Safety Code.
History
1. Amendment filed 7-6-2004; operative 7-6-2004 pursuant to Government Code section 11343.4 (Register 2004, No. 28).
This database is current through 5/3/24 Register 2024, No. 18.
Cal. Admin. Code tit. 25, § 1268, 25 CA ADC § 1268