§ 1186. Lot Receptacles.
(a) A receptacle used to supply electrical energy to a unit shall conform with the American National Standards Institute-National Electrical Manufacturers Association (ANSI-NEMA) Standard, WD-6, 1997 for one of the following configurations:
(1) 125/250 volts, 50-amperes, 3 pole, 4 wire, grounding type for 120/240 volt systems.
(2) 125 volts, 30-amperes, 2 pole, 3 wire, grounding type for 120 volt systems.
(3) 125 volts, 20-amperes, 2 pole, 3 wire, grounding type for supplying units having only one 15 or 20-ampere branch circuit.
(b) ANSI-NEMA Standards may be obtained on-line from www.nema.org or by calling (703) 841-3200 or by writing to NEMA, Communications Department, 1300 North 17th Street, Rosslyn, Virginia, 22209.

Credits

Note: Authority cited: Section 18300, Health and Safety Code. Reference: Section 18670, Health and Safety Code.
History