§ 1154. Primary System Grounding--600 Volts or Less.
(a) When the park electrical service is supplied by a grounded system operated at 600 volts or less, an equipment grounding conductor shall be run with the feeders of the park primary electrical system to all equipment supplied by the primary electrical system.
(b) Park primary electrical systems within the park operated at 600 volts or less supplied by an ungrounded system shall not be grounded.

Credits

Note: Authority cited: Section 18300, Health and Safety Code. Reference: Section 18670, Health and Safety Code.