§ 1148. Overcurrent Protection.
25 CA ADC § 1148Barclays Official California Code of Regulations
25 CCR § 1148
§ 1148. Overcurrent Protection.
(a) Conductors shall be protected by overcurrent protective devices. A fuse or circuit breaker rating shall not be greater than the allowable ampacity of the conductors to be protected as specified in Tables 310-16 through 310-19 found in the California Electrical Code, except as provided in Articles 210, 240, and 430.
(b) All electrical equipment and devices, including service equipment, transformers and receptacles, shall be protected by overcurrent protective devices rated at not more than the rating of the equipment or device, except as provided in Articles 210, 240, 430, and 450 of the California Electrical Code.
Credits
Note: Authority cited: Section 18300, Health and Safety Code. Reference: Section 18670, Health and Safety Code.
History
1. Amendment filed 7-6-2004; operative 7-6-2004 pursuant to Government Code section 11343.4 (Register 2004, No. 28).
This database is current through 5/10/24 Register 2024, No. 19.
Cal. Admin. Code tit. 25, § 1148, 25 CA ADC § 1148
End of Document |