Home Table of Contents

§ 1136. Conductors and Equipment.

25 CA ADC § 1136Barclays Official California Code of Regulations

Barclays California Code of Regulations
Title 25. Housing and Community Development
Division 1. Housing and Community Development
Chapter 2. Mobilehome Parks and Installations
Article 3. Electrical Requirements
25 CCR § 1136
§ 1136. Conductors and Equipment.
(a) 600 volts or less. For purposes of this chapter, all electrical conductors and equipment rated at 600 volts or less, installed outside of permanent buildings in park electrical wiring systems constructed, or approved for construction, shall be listed and labeled as approved for their intended use.
(b) Greater than 600 volts. Conductors and equipment installed in systems operated at more than 600 volts shall comply with the applicable provisions contained in the California Electrical Code, Article 490, and the High Voltage Safety Orders contained in Title 8, California Code of Regulations, Chapter 4, Subchapter 5, Group 2.
(c) A grounded neutral conductor may be a bare conductor when properly isolated from phase conductors. A bare neutral conductor, or a bare concentric stranded conductor of a cable used as a grounded neutral conductor, shall be copper when installed underground. These types of systems shall be solidly grounded.

Credits

Note: Authority cited: Section 18300, Health and Safety Code. Reference: Section 18670, Health and Safety Code.
History
1. Amendment filed 8-22-85; effective upon filing pursuant to Register 85, No. 36.
2. Amendment of section heading and section filed 7-6-2004; operative 7-6-2004 pursuant to Government Code section 11343.4 (Register 2004, No. 28).
This database is current through 5/10/24 Register 2024, No. 19.
Cal. Admin. Code tit. 25, § 1136, 25 CA ADC § 1136
End of Document