Table 5 Hydrostatic Test Interval for Extinguishers
19 CA ADC Table 5Barclays Official California Code of Regulations
19 CCR Table 5
Table 5 Hydrostatic Test Interval for Extinguishers
Extinguisher type | Test Interval (Years) |
Stored Pressure Water and/or Antifreeze/Loaded Stream | 5 | |
AFFF (Aqueous Film Forming Foam) | 5 | |
FFFP (Film Forming Fluoroprotein Foam) | 5 | |
Wet Chemical | 5 | |
Dry Chemical with Stainless Steel Shells | 5 | |
Carbon Dioxide | 5 | |
Dry Chemical, Stored Pressure with Mild Steel Shells, Brazed Brass Shells, or Aluminum Shells | 12 | |
Dry Chemical, Cartridge and Cylinder-Operated, with Mild Steel Shells | 12 | |
Halogenated Agents | 12 | |
Dry Powder, stored pressure, cartridge- or cylinder-operated with mild steel shells | 12 |
Credits
Note: Authority: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.