Home Table of Contents

§ 572. Size and Placement for Class D Hazards.

19 CA ADC § 572Barclays Official California Code of Regulations

Barclays California Code of Regulations
Title 19. Public Safety
Division 1. State Fire Marshal
Chapter 3. Fire Extinguishers
Article 5. Selection and Distribution of Portable Fire Extinguishers
19 CCR § 572
§ 572. Size and Placement for Class D Hazards.
(a) Fire extinguishers or extinguishing agents with Class D ratings shall be provided for fires involving combustible metals.
(b) Fire extinguishers or extinguishing agents (media) shall be located not more than 75 ft (22.5 m) travel distance from the Class D hazard.
(c) Portable fire extinguishers or extinguishing agents (media) for Class D hazards shall be provided in those work areas where combustible metal powders, flakes, shavings, chips, or similarly sized products are generated.
(d) Size determination shall be in the basis of the specific combustible metal, its physical particle size, area to be covered and recommendations by the extinguisher manufacturer on data from control tests conducted.
(e) The material safety data sheet for the Class D hazard involved should be consulted to assist in selecting the most effective extinguishing agent.

Credits

Note: Authority: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.
History
1. New section filed 3-4-92; operative 4-3-92 (Register 92, No. 15).
2. Amendment filed 12-27-2001; operative 1-1-2002 pursuant to Government Code section 11343.4 (Register 2001, No. 52).
This database is current through 5/3/24 Register 2024, No. 18.
Cal. Admin. Code tit. 19, § 572, 19 CA ADC § 572
End of Document