§ 571. Fire Extinguisher Size and Placement for Class C Hazards.
19 CA ADC § 571Barclays Official California Code of Regulations
19 CCR § 571
§ 571. Fire Extinguisher Size and Placement for Class C Hazards.
(a) Fire extinguishers with Class C ratings shall be required where energized electrical equipment can be encountered which would require a nonconducting extinguishing medium. This requirement includes situations where fire either directly involves or surrounds electrical equipment. Since the fire itself is a Class A or Class B hazard, the fire extinguishers shall be sized and located on the basis of the anticipated Class A or B hazard.
Note: Electrical equipment should be de-energized as soon as possible to prevent reigniting.