007.10.26-V. Water Supply Design and Operation
AR ADC 007.10.26-VArkansas Administrative Code
Ark. Admin. Code 007.10.26-V
007.10.26-V. Water Supply Design and Operation
B. Prior to placing the water supply system into use, all portions of the system shall be disinfected by adding a chlorine solution of not less than 50 ppm and retaining the mixture within all portions of the system for at least 24 hours. Following disinfection, the system is to be flushed thoroughly of the chlorine solutions, and then bacteriological water samples shall be collected daily and submitted to the State Department of Health until two consecutive samples show the water to be safe for drinking.
Credits
Amended July 8, 2010.
Current with amendments received through February 15, 2024. Some sections may be more current, see credit for details.
Ark. Admin. Code 007.10.26-V, AR ADC 007.10.26-V