235.02.1-602. State Installation Specifications
AR ADC 235.02.1-602Arkansas Administrative CodeEffective: August 17, 2020
Effective: August 17, 2020
Ark. Admin. Code 235.02.1-602
Formerly cited as AR ADC 066.00.1-6
235.02.1-602. State Installation Specifications
3. Soil classification and bearing capacity of the soil must be determined before the foundation is constructed and anchored. Soil classification and bearing capacity may be determined by one or more of the following methods, unless the soil bearing capacity is established as permitted in (f) of this section:
Soil Classification | |||||
---|---|---|---|---|---|
Classification Number | ASTM D 2478-00 or D 2488-00 | Soil Description | Allowable Soil Bearing Pressure PSF | Blow Count ASTM D 1586-99 | Torque Probe Value (inch-pounds) |
1 | Rock or Hard Pan | 4000 + | |||
2 | GW, GP, SW, SP, GM, SM | Sandy Gravel & Gravel; Very Dense and/or Cemented Sands; Coarse Gravel/Cobbles; Preloaded Silts, Clays & Corals | 2000 | 40 + | More Than 550 |
3 | GC, SC, ML, CL | Sand; Silty Sand; Clayey Sands; Silty Gravel; Medium Dense Coarse Sands; Sandy Gravel; and Very Stiff Silt, Sand Clays | 1500 | 24-39 | 351-550 |
4A | CG. MH2 | Loose to Medium Dense Sands; Firm to Stiff Clays & Silts; Alluvial Fills | 1000 | 18-23 | 276-350 |
4B | CH, MH2 | Loose Sands; Firm Clays; Alluvial Fills | 1000 | 12-17 | 175-275 |
5 | OL, OH. PT | Uncompacted Fill; Peat; Organic Clays | 0-11 | Less Than 175 |
3. The surface texture of poured concrete footings at each pier location shall be such that the first pier block placed at these locations shall sit firmly and evenly. If a firm, level contact between the first pier block and the surface of the footing is not possible because of surface irregularities in the footing; masonry mortar shall be used between the entire bottom surface of the first pier block and the footing to establish a solid interface contact which is level.
FOOTER SIZING TABLE
Based on Soil Bearing Capacity
Opening Size | 1000 PSF | 1500 PSF | 2000 PSF | 4000 PSF |
---|---|---|---|---|
4′ -- 8′ | 400 sq in | 256 sq in | 256 sq in | 256 sq in |
8′ -- 16′ | 576 sq in | 400 sq in | 256 sq in | 256 sq in |
16′ -- 20′ | 784 sq in | 576 sq in | 400 sq in | 256 sq in |
20′ -- 28′ | 1156 sq in | 784 sq in | 576 sq in | 256 sq in |
I-Beam Footers (8′ Max Spacing) | 576 sq in | 400 sq in | 256 sq in | 256 sq in |
Piers shall be constructed of eight inches by eight inches by sixteen inches (8″ x 8″ x 16″) concrete building blocks, open celled, solid, or equivalent which meet or exceed the specifications per ASTM C90, ground-contact rated. Open celled blocks shall be installed with the open cells vertical.
c. Additional pressure preservative treated wooden shims with a minimum width of five and one-half inches (5 1/2″) and a minimum length of twelve inches (12″) and a minimum thickness of one-quarter inch (1/4″) and a maximum thickness of one inch (1″) may be used between the wood plate and the I-beam.
d. Hardwood wedges with a minimum width of four inches (4″) and a minimum length of six inches (6″) and a maximum installed thickness of one inch (1″) may be used if placed directly between the last wooden member of the pier and the point of support. Wedges shall be centered and driven tight from both sides of the I-beam or marriage line perimeter joists.
a. The marriage line of multi-section manufactured homes shall be supported by piers located no more than eight feet (8′) apart on center and shall have piers located within two feet of each end of the marriage line. In addition to these piers, multi-section homes shall have piers located under the jamb studs or ridge beam column posts for openings in the marriage wall of four feet (4′) or greater.
a. Floor sections shall be connected with lag bolts of at least five-sixteenths inch (5/16″), and of sufficient length to penetrate into the opposing floor joist at least three-quarters inch (3/4″). Lag bolts shall be installed no more than twenty inches (20″) apart on center, alternating sides. Bolting must not dislodge the rim joist.
d. Air conditioning cross-over ducts shall be attached to each plenum with screws and wire ties and taped to prevent air loss. The duct shall be suspended above the ground and fastened in place. Ties or straps used to suspend the duct shall not crush or crimp the duct in a manner that substantially reduces airflow.
Credits
Amended Oct. 20, 2013; Aug. 19, 2016; Jan. 29, 2017; Aug. 17, 2020.
Current with amendments received through May 15, 2024. Some sections may be more current, see credit for details.
Ark. Admin. Code 235.02.1-602, AR ADC 235.02.1-602
End of Document |