007.05.10-59. Physical Facilities, Dietary Facilities.
AR ADC 007.05.10-59Arkansas Administrative Code
Ark. Admin. Code 007.05.10-59
007.05.10-59. Physical Facilities, Dietary Facilities.
Construction, equipment, and installation shall comply with the standards specified in FDA U.S. Public Health Service Food Code. Food service facilities shall be designed and equipped to meet the requirements of the functional program. These may consist of an onsite conventional food preparing system, a convenience food service system, or an appropriate combination of the two. The following shall be provided:
B. Storage Spaces. A minimum of four days' supplies shall be stocked. (In remote areas, this number may be increased to accommodate length of delivery in emergencies). All food shall be stored clear of the floor. Lowest shelf shall not be less than 12 inches above the floor or shall be closed in and sealed tight for ease of cleaning;
D. Food Preparation Facilities. Conventional food preparation systems shall have adequate space and equipment for preparing, cooking, and baking. Convenience food preparation systems shall have adequate space for equipment for thawing, portioning, cooking, and/or baking. These areas shall be as close as possible to the user (i.e., tray assembly and dining);
F. Food Service Carts. A cart distribution area shall provide space for storage, loading, distribution, receiving, and sanitizing of food service carts. The cart traffic shall be designed to eliminate any danger of cross circulation between outgoing food carts and incoming, soiled carts, and the cleaning and sanitizing process. Cart circulation shall not traffic through food processing areas;
J. Dishwashing Space. An area shall be located in a room separate from food preparation and serving areas. Commercial-type dishwashing equipment shall be provided. Clean and soiled dish areas shall be separated with an opening in the partition between the clean and soiled dish area large enough for the dishwasher and ventilation of the area. The clean dish area may be either a separate room or a portion of the kitchen. A lavatory shall be conveniently available. The soiled dish area shall be so located as to prevent soiled dishes from being carried through the food preparation area;
N. Storage Rooms and Areas. A room for cans, carts, mobile tray conveyors, and cleaning and sanitizing carts shall be provided. There shall be a separate storage room for the storage of non-food items that might contaminate edibles (i.e., cleaning supplies). A separate space or room for the storage of cooking wares, extra trays, flatware, plastic and paper products, and portable equipment is required;
Q. Environmental Closet. A closet shall be provided for the exclusive use of the dietary department to contain a floor sink and space for mops, pails, and supplies. Where hot water or steam is used for general cleaning, additional space within the room shall be provided for the storage of hoses and nozzles;
S. Commissary or Contract Services from Other Areas. If a service is used, above items may be reduced as appropriate. The process of food delivery shall insure freshness, retention of hot and cold, and avoidance of contamination. If delivery is from outside sources, protection against weather shall be provided. Provisions shall be made for thorough cleaning and sanitizing of equipment to avoid mix of soiled and clean equipment;
T. Equipment. Mechanical devices shall be heavy duty, suitable for intended use and easily cleaned. Movable equipment shall have heavy duty locking casters. If equipment is to have fixed utility connections, it shall not be equipped with casters. Walk-in coolers, refrigerators, and freezers shall be insulated at floor, walls and top. Coolers and refrigerators shall be capable of maintaining a temperature down to freezing. Freezers shall be capable of maintaining a temperature of 20° below zero Fahrenheit. Coolers, refrigerators, and freezers shall be thermostatically controlled to maintain desired temperature settings in increments of two degrees or less. Interior temperatures shall be visible from the exterior. Controls may include audible and visible high and low temperature alarm. Time of alarm shall be automatically recorded. Walk-in units may be lockable from outside but shall have release mechanism for exit from inside at all times. Interior shall be lighted. All shelving shall be corrosion resistant, easily cleaned, and constructed and anchored to support a loading of at least 100pounds per linear foot. All cooking equipment shall be equipped with automatic shut off devices to prevent excessive heat buildup. Under counter conduits, piping, and drains shall be arranged to not interfere with cleaning of floor below or of the equipment;
Credits
Amended Jan. 1, 2016.
<Statutory authority: Promulgated under the Authority of Ark. Code Ann. § 20-7-123, 20-9-201 et seq.>
Current with amendments received through February 15, 2024. Some sections may be more current, see credit for details.
Ark. Admin. Code 007.05.10-59, AR ADC 007.05.10-59
End of Document |