007.04.10-20. System Design
AR ADC 007.04.10-20Arkansas Administrative CodeEffective: May 12, 2022
Effective: May 12, 2022
Ark. Admin. Code 007.04.10-20
007.04.10-20. System Design
20.4 The spacing between drip tube laterals shall not be less than two (2) ft. center to enter. Drip tube laterals spacing may be greater than two (2) ft. however, for the purpose of determining the length of tubing required for a dispersal field, all length calculation shall be two (2) ft. center to center.
20.5 The effective area of the dispersal field shall be calculated by dividing the daily wastewater flow rate (DWF) in gallons per day (gpd) by the soil loading rate (SLR) in gallons per foot square per day (g/ft ft2 / d). [Area of the dispersal field (DF) = design wastewater flow (DWF) / soil loading rate (SLR).]
Credits
Adopted July 8, 2010. Amended May 12, 2022.
Current with amendments received through February 15, 2024. Some sections may be more current, see credit for details.
Ark. Admin. Code 007.04.10-20, AR ADC 007.04.10-20